SC25 in St. Louis looked like a plumbing convention had crashed the supercomputing hall. Pipes, pumps, manifolds, and quick-disconnects were everywhere, along with people who clearly spend more time thinking about pressure drop than floating-point. I kept expecting to see a booth selling industrial fire hoses.
Chicago is a much bigger venue. McCormick has roughly four times the exhibit space St. Louis had, so the pre-show question was whether SC26 would look the same or whether the hall was large enough to dilute the effect. If anything, cooling was even more dominant in Chicago. The heat problem didn't get smaller just because the building got bigger.
We also saw many new companies displaying cooling products at SC26. I follow this market closely and see two broad trends. The first is consolidation, with large industrial suppliers buying up the liquid-cooling pioneers. The second is that anyone with an angle is entering the market. Both trends were visible on the Chicago floor, and everyone had something to say about higher inlet temperatures, whether or not they had a real story.
**Game-changing news**
The real news is a number Nvidia released earlier this year: a 45°C (113°F) liquid inlet temperature for its parts. That is not a small tweak. Most liquid-cooled systems have operated in the 30–35°C (86–95°F) range because that is what the chips would tolerate. Moving to 45°C (113°F) means many datacenters that currently need chillers suddenly won't.
If AMD, Intel, and the Arm players can match it, and we would be shocked if they aren't already working on exactly that, then free cooling stops being a feature of cool climates and becomes the default for many more locations.
Rooftop dry coolers can reject almost any incoming fluid temperature and bring it below 45°C (113°F). Few places in the world have ambient temperatures approaching 113°F, and for the hours when outside temperatures spike, adiabatic assist is available. This involves trickling water through a mesh surrounding the dry coolers, which lowers the effective temperature another 10–20 percent.
The resulting cooling architecture has two closed loops. The first takes heat from the server equipment and passes it to a second, separate loop. That loop carries the hot water to the roof, cools it, and returns it.
What's missing from this picture is the chiller. You won't need one anymore. Chillers are essentially huge rooftop refrigerators that cool water further after dry cooling. They are expensive, require significant maintenance, consume a lot of electricity, and are no longer necessary for new datacenter builds.
The power and water savings are substantial. Legacy designs that rely on chillers and open evaporative towers commonly devote 20 to 40 percent of total facility energy to cooling. A large share of that goes to the chiller plant itself: compressors, pumps, and cooling-tower fans. Moving to dry coolers running at a 45°C (113°F) inlet collapses that slice.
Published estimates and vendor modeling for high-temperature liquid loops put the reduction in cooling energy at 50 to 70 percent compared with a conventional chiller-plus-tower plant. That translates into a 10 to 20 percent drop in total datacenter power, depending on the starting PUE (Power Usage Effectiveness) and climate.
Water use falls even more sharply. Traditional evaporative towers can consume millions of gallons a year at a mid-size site. Dry coolers use essentially no outside water in normal operation, and adiabatic assist wets the mesh only during the hottest hours. This cuts annual water consumption by 80 to 95 percent in most climates. These are the numbers that make the 45°C (113°F) inlet such a big deal.
The same shift changes the economics of the mechanical plant itself. A chiller plant is not just an operating cost. It is capital equipment that must be sized, installed, maintained, and eventually replaced. Dry coolers are simpler, cheaper to install, and have far fewer moving parts. When chips accept 45°C (113°F) fluid, the business case for a mechanical refrigeration plant on the roof of a new build becomes hard to defend in most climates. This is the part that has not yet fully registered outside the cooling specialists.
**Getting to 45°C isn't free**
Designing systems around higher inlet temperatures still requires real engineering work: sizing the loops, selecting the dry coolers, and ensuring the facility can run at the new setpoints without surprises. Existing buildings add another layer. Many were built with pipes, pumps, and heat exchangers sized for air cooling or lower-temperature liquid. Raising the liquid inlet temperature means checking flow rates and pressure drops and confirming that the existing setup delivers.
At SC26, I met with several companies that do this work and buttonholed more at their booths. My top-of-mind questions were these.
Are the 45°C (113°F) inlet temperatures real? Yes. They are being used as a design basis to an extent, though designers need to leave headroom.
Has anyone heard whether the other chipmakers will hit Nvidia's inlet temperature number? Attendees were closed-lipped on this one. There was nothing public from AMD, Intel, or Arm. On the cooling-vendor side, however, people are happy to see the increase and will comply.
My instincts tell me the other chipmakers may have been caught flat-footed by Nvidia's 45°C stake in the ground. Those same instincts also tell me that handfuls of Peanut M&Ms are healthy snacks. I'll nose around more.
There is real money at stake from a total-cost-of-ownership standpoint. One cooling vendor reports that its initial testing shows a 3 to 4 percent decrease in cooling energy cost for every additional 1°C of inlet temperature increase. At scale, that is significant.
We are approaching a point where industry advances answer many of the objections raised by the anti-datacenter movement, at least the real ones rather than the hysterical ones. Energy use goes down, water consumption falls by 85 to 90 percent, efficiency rises, and costs drop. Not a bad deal, right?